Hospital isolation rooms
Contents |
[edit] Introduction
Isolation rooms for the prevention of airborne infection are an integral part of hospitals, ensuring immuno compromised patients are protected from infection and infectious patients are isolated. They are designed in accordance with the biosafety level of the pathogens they are likely to contain or isolate from.
Effective isolation rooms require careful consideration and in recent years BSRIA has assisted the Department of Health in improving their design validation practice.
[edit] New space design is helping patients’ protection
Pressure differentials isolate the rooms from the rest of the hospital. Positively pressurised rooms tend to be used to protect patients that have been immuno compromised, whereas negative isolation rooms are used to isolate an infectious patient. Air flows from a higher pressurised space into a lower pressurised space, so in positive isolation rooms, the patient is protected from infections occurring elsewhere in the hospital. In the case of negative isolation rooms, air cannot flow from the room into the hospital, therefore isolating the infection, but consideration must be given to the protection of the patient from a different infection. In recent years, new designs incorporating a Positively Pressurised Ventilated Lobby (PPVL) and neutral patient rooms have been described by the Department of Health in HBN4 (Isolation facilities for infectious patients in acute settings) and tested and validated by BSRIA.
A PPVL, set at a higher pressure than both the patient’s room and the hospital corridor, prevents air from the corridor entering the patient’s room, therefore protecting the patient, and at the same time preventing air from the room, and from a potentially infectious patient, to flow into the corridor. In addition, these rooms incorporate an “en suite” bathroom, at a negative pressure with respect to the patient’s room, ensuring all air is extracted through the “en suite” and filtered prior to release outside.
The pressure differentials in these rooms tend to be in the order of 10 Pa. Pressure differentials do not need to be as large as in other applications to ensure air flows in the desired direction. In practice, very large pressure differentials could make the doors more difficult to open and would mean higher leakage rate of potentially contaminated air in the event of poor airtightness of the room.
[edit] Good airtightness helps achieve effective isolation
Good airtightness will assist in commissioning the rooms, ensuring pressure stabilisers work properly, rooms are pressurised, and AHU are operating within the design envelope. By ensuring the structure leaks as little as possible, it is easier to achieve design pressures.
In the event of fan failure, even if it is temporary, the walls of the room constitute the first line of defence against airborne infection. Building for airtightness ensures, that in the event of fan failure, there are not-unaccounted-for flows of potentially contaminated air flowing into areas that are, in principle, risk free. E.g. in a 10 Pa pressure differential, an airtightness of 1 m³/h/m² would equate to 60 l/s of air (which is equivalent to having another door) flowing from the isolation room into other areas of the hospital, where people may not be wearing PPE. A good (low) level of airtightness is much easier to achieve if it is considered through design and the constructions stages.
[edit] BSRIA standard on Air permeability of isolation rooms (BTS3) forms part of NHS guidance HBN4
A methodology for testing the airtightness of isolation rooms has been described in BSRIA’s technical standard 'BTS 03: Air permeability of isolation rooms' and has been included in the NHS guidance to isolation rooms 'HBN4 Isolation facilities for infectious patients in acute settings'.
Nowadays, we could be talking about entire hospital wings dedicated to isolation. In this case, the PPVL and airtightness principles could be applied as well to ensure that the patients are properly isolated as well as protected.
Click here to download a copy of BSRIA's Air permeability testing of isolation facilities (BTS 3/2018) Standard.
This article was originally published on the BSRIA blog in March 2020, it was written by Dr Blanca Beato-Arribas, BSRIA Microclimate Team Leader.
--BSRIA
[edit] Related articles on Designing Buildings
- Air change rate.
- Air permeability in isolation rooms.
- Air permeability testing.
- Air permeability testing of isolation facilities.
- Air permeability.
- BSRIA articles on Designing Buildings Wiki.
- BSRIA.
- Clean indoor air for healthy living - New air filter standards.
- Coronavirus.
- Design of isolation rooms for infection control.
- Emergency healthcare architecture in Brazil.
- Indoor air quality.
Featured articles and news
Retrofit 25 – What's Stopping Us?
Exhibition Opens at The Building Centre.
Types of work to existing buildings
A simple circular economy wiki breakdown with further links.
A threat to the creativity that makes London special.
How can digital twins boost profitability within construction?
The smart construction dashboard, as-built data and site changes forming an accurate digital twin.
Unlocking surplus public defence land and more to speed up the delivery of housing.
The Planning and Infrastructure Bill
An outline of the bill with a mix of reactions on potential impacts from IHBC, CIEEM, CIC, ACE and EIC.
Farnborough College Unveils its Half-house for Sustainable Construction Training.
Spring Statement 2025 with reactions from industry
Confirming previously announced funding, and welfare changes amid adjusted growth forecast.
Scottish Government responds to Grenfell report
As fund for unsafe cladding assessments is launched.
CLC and BSR process map for HRB approvals
One of the initial outputs of their weekly BSR meetings.
Architects Academy at an insulation manufacturing facility
Programme of technical engagement for aspiring designers.
Building Safety Levy technical consultation response
Details of the planned levy now due in 2026.
Great British Energy install solar on school and NHS sites
200 schools and 200 NHS sites to get solar systems, as first project of the newly formed government initiative.
600 million for 60,000 more skilled construction workers
Announced by Treasury ahead of the Spring Statement.
The restoration of the novelist’s birthplace in Eastwood.
Life Critical Fire Safety External Wall System LCFS EWS
Breaking down what is meant by this now often used term.
PAC report on the Remediation of Dangerous Cladding
Recommendations on workforce, transparency, support, insurance, funding, fraud and mismanagement.
New towns, expanded settlements and housing delivery
Modular inquiry asks if new towns and expanded settlements are an effective means of delivering housing.